210 
The  method  is  advanced  with  easy  program  and  quick  calculation  speed.  But  the  ROM 
space  the  program  occupied  is  huge.  So  use  it  with  caution  according  to  the  program 
required space.   
10.4 RTU command code and communication data illustration   
10.4.1 command code:03H 
03H(correspond  to binary 0000  0011),read N words(Word)(the  Max.  continuous 
reading is 16 words) 
Command  code  03H  means  that  if  the  master  read  data  form  the  inverter,  the  reading 
number depends on the “data number” in the command code. The Max. continuous reading 
number  is 16  and the parameter  address should be  continuous. The byte  length  of  every 
data is 2 (one word). The following command format is illustrated by hex (a number with “H” 
means hex) and one hex occupies one byte.   
The command code is used to read the working step of the inverter. 
For example, read continuous 2 data content from0004H from the inverter with the address 
of  01H (read the content  of data  address  of  0004H  and 0005H), the frame  structure  is  as 
below:   
RTU master command message (from the master to the inverter) 
START  T1-T2-T3-T4 (transmission time of 3.5 bytes) 
ADDR  01H 
CMD  03H 
High bit of the start bit  00H 
Low bit of the start bit  04H 
High bit of data number  00H 
Low bit of data number  02H 
CRC low bit    85H 
CRC high bit    CAH 
END  T1-T2-T3-T4 (transmission time of 3.5 bytes) 
T1-T2-T3-T4 between START  and END is to  provide at  least the  time  of 3.5 bytes  as the 
leisure time and distinguish two messages for the avoidance of taking two messages as one 
message.   
ADDR = 01H means the command message is sent to the inverter with the address of 01H 
and ADDR occupies one byte 
CMD=03H means the command  message  is sent to read data form  the inverter  and CMD