Goodrive200 inverters Basic operation instruction
176
Function
code
Name Detailed instruction of parameters
Default
value
P09.12
F
eedback offline detection
time
0.0~3600.0s
1.0s
P09.13 PID adjustment
0x00~0x11
LED ones:
0:Keep the integral adjustment ON while
the frequency achieves upper or lower
limit.
1:Stop the integral adjustment while the
frequency achieves the upper or lower
limit
LED tens:
0:The same with the setting direction
1:Opposite to the setting direction
0x00
P17.00
Set frequency
0.00Hz~P00.03 (the Max. frequency)
0.00Hz
P17.23 PID reference value
-100.0~100.0% 0.0%
P17.24 PID feedback value -100.0~100.0% 0.0%
7.14 Traverse running
Traverse is applied in some industries such as textile, chemical fiber and cases where traverse and
convolution is required. The working flowchart is as below: