Goodrive200 inverters Basic operation instruction
130
When the user selects the user-defined V/F curve function in Goodrive200 series inverters, they
can set the reference channel of voltage and frequency and the corresponding ACC/DEC time, or
the two can combinate to form a real-time curve.
Note: the application of V/F curve separation can be used in many cases with various kinds of
power supply of the inverter. But the users should set and adjust the parameters with caution.
Incorrect parameters may cause damage to the inverter.
Function
code
Name
Detailed instruction of parameters Default
value
P00.00 Speed control mode
2:V/F control (applying to AM)
0
P00.03 Max. output frequency
Setting range: P00.04~400.00Hz 50.00Hz
P00.04
Upper limit of the running
frequency
Setting range:P00.05~P00.03 (Max.
output frequency)
50.00Hz
P00.05
Lower limit of the running
frequency
Setting range:0.00Hz~P00.04 (Upper
limit of the running frequency)
0.00Hz
P00.11 ACC time 1 0.0~3600.0s
Depend
on model
P00.12 DEC time 1 0.0~3600.0s
Depend
on model
P02.02
Asynchronous motor 1
rated frequency
0.01Hz~P00.03(the Max. frequency) 50.00Hz
P02.04
Asynchronous motor 1
rated voltage
0~1200V
Depend
on model
P04.00 Motor 1 V/F curve setting
0:Straight line V/F curveapplying to the
constant torque load
1:Multi-dots V/F curve
2:1.3
th
power low torque V/F curve
3:1.7
th
power low torque V/F curve
4:2.0th power low torque V/F curve
5:Customized V/F(V/F separation)
0
P04.01 Motor 1 torque boost
0.0%:(automatic)0.1%~10.0% 0.0%
P04.02 Motor 1 torque boost close
0.0%~50.0%(the rated frequency of
motor 1)
20.0%
P04.03 Motor 1 V/F 0.00Hz~P04.05 0.00Hz