Goodrive200 inverters Product overview
14
Function Specification
150% of rated current: 1 minute
180% of rated current: 10 seconds
200% of rated current: 1 second
P type:
120% of rated current: 60 second
Frequency setting
Digital setting, analog setting, pulse frequency
setting, multi-step speed running setting, simple
PLC setting, PID setting, MODBUS communication
setting, PROFIBUS communication setting.
Realize the shifting between the set combination
and set channel.
Auto voltage
adjustment
Keep a stable voltage automatically when the grid
voltage transients
Fault protection
Provide over 30 fault protection functions:
overcurrent, overvoltage, undervoltage, overheating,
phase loss and overload, etc.
Running
control
feature
Speed tracking Restart the rotating motor smoothly
Terminal analog input
resolution
≤ 20mV
Terminal switch input
resolution
≤ 2ms
Analog input
2 channels (AI1, AI2) 0~10V/0~20mA and 1 channel
(AI3) -10~10V
Analog output 2 channels (AO1, AO2) 0~10V /0~20mA
Digital input
8 channels common input, the Max. frequency:
1kHz, internal impedance: 3.3kΩ;
1 channel high speed input, the Max. frequency:
50kHz
Digital output
1 channel high speed pulse output, the Max.
frequency: 50kHz;
1 channel Y terminal open collector pole output
Peripheral
interface
Relay output 2 channels programmable relay output