Goodrive200 inverters Basic operation instruction
166
200ms
200ms
Digital output 15
Simple PLC stage completion
Digital output 20
Simple PLC cycle completion
Relative parameters list:
Function
code
Name Detailed instruction of parameters
Default
value
P10.00 Simple PLC
0:Stop after running once
1:Run at the final value after running
once
2:Cycle running
0
P10.01 Simple PLC memory
0:Power loss without memory
1:Power loss memory
0
P10.02 Multi-step speed 0 -100.0~100.0% 0.0%
P10.03 The running time of step
0
0.0~6553.5s(min)
0.0s
P10.04 Multi-step speed 1 -100.0~100.0% 0.0%
P10.05 The running time of step
1
0.0~6553.5s(min) 0.0s
P10.06 Multi-step speed 2 -100.0~100.0% 0.0%
P10.07 The running time of step
2
0.0~6553.5smin 0.0s
P10.08 Multi-step speed 3 -100.0~100.0% 0.0%
P10.09 The running time of step
3
0.0~6553.5s(min) 0.0s
P10.10 Multi-step speed 4 -100.0~100.0% 0.0%
P10.11 The running time of step 4
0.0~6553.5smin 0.0s
P10.12 Multi-step speed 5 -100.0~100.0% 0.0%
P10.13 The running time of step
5
0.0~6553.5s(min) 0.0s
P10.14 Multi-step speed 6 -100.0~100.0% 0.0%
P10.15 The running time of step
6
0.0~6553.5s(min) 0.0s