application will be mentioned in 10.8 with examples.
10.4.3 Command code 08H for diagnosis
Meaning of sub-function codes
Sub-function Code Description
0000 Return to inquire information data
For example: The inquiry information string is same as the response information string when
the loop detection to address 01H of driver is carried out.
The RTU request command is:
START T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR 01H
CMD 08H
High byte of sub-function code 00H
Low byte of sub-function code 00H
High byte of data content 12H
Low byte of data content ABH
Low byte of CRC ADH
High byte of CRC 14H
END T1-T2-T3-T4 (transmission time of 3.5 bytes)
The RTU response command is:
START T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR 01H
CMD 08H
High byte of sub-function code 00H
Low byte of sub-function code 00H
High byte of data content 12H
Low byte of data content ABH
Low byte of CRC ADH
High byte of CRC 14H
END T1-T2-T3-T4 (transmission time of 3.5 bytes)
10.4.4 The definition of data address
The address definition of the communication data in this part is to control the running of the