Goodrive200 inverters Installation guidelines
30
Fig 4-17 350~500kW terminals of main circuit
Terminal name
Terminal
≤30kW ≥37kW
Function
R, S, T
Power input of the main circuit
3-
phase AC input terminals which are
generally connected with the
power
supply.
U, V, W
The inverter output
3-
phase AC output terminals which are
generally connected with the motor.
P1
This terminal is
inexistent
DC reactor terminal 1
(+)
Braking
resistor
1
DC reactor terminal 2
,
braking unit terminal 1
(-) / Braking unit terminal 2
PB
Braking resistor
terminal 2
This terminal is
inexistent.
P1 and (+) are c
onnected with the
terminals of DC reactor.
(+) and (-)
are connected with the
terminals of braking unit.
PB and (+)
are connected with the
terminals of braking resistor.
PE
380V:
the grounding resistor is less
than 10Ohm
Protective grounding
terminals, every
machine is provided 2 PE terminals
as