Goodrive200 inverters Function codes
63
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modify
speed, it is not necessary to adjust the protection
value during low-speed running.
P02.27
M
otor 1 over
load
protection
coefficient
W
hen P02.27=overload protection current of the
motor/rated current of the motor
S
o, the bigger the overload coefficient is, the shorter
the reporting time of the overload fault is. When the
overloa
d coefficient <110%, there is no overload
protection. When the overload
coefficient =116%,
the fault will be reported after 1 hour, when the
overload coefficient=200%, the fault will be reported
after 1 minute.
Setting range: 20.0%~120.0%
100.0%
P02.28
Reserved
P02.29
Reserved
P03 Group Vector control
P03.00
Reserved
P03.01
Reserved
P03.02
Reserved
P03.03
Reserved
P03.04
Reserved