Goodrive200 inverters Function codes
Name
Detailed instruction of parameters
Default
value
speed, it is not necessary to adjust the protection
value during low-speed running.
P02.27
hen P02.27=overload protection current of the
motor/rated current of the motor
S
o, the bigger the overload coefficient is, the shorter
the reporting time of the overload fault is. When the
d coefficient <110%, there is no overload
protection. When the overload
the fault will be reported after 1 hour, when the
overload coefficient=200%, the fault will be reported
after 1 minute.
Setting range: 20.0%~120.0%
100.0%
●
P03 Group Vector control
P03.00