Goodrive35 inverters Function codes
119
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
LED thousands: / keys and digital
potentiometer integral function
0: The integral function is valid
1: The integral function is invalid
P08.43
Integral
ratio of the
keypad
potentiome
ter
0.01~10.00Hz/s
0.10
Hz/s
P08.44
UP/DOWN
terminals
control
0x000~0x221
LED ones: frequency control selection
0:UP/DOWN terminals setting valid
1:UP/DOWN terminals setting valid
LED tens: frequency control selection
0:Only valid when P00.06=0 or P00.07=0
1:All frequency means are valid
2:When the multi-step are priority, it is invalid to the
multi-step
LED hundreds: action selection when stop
0:Setting valid
1: Valid in the running, clear after stop
2: Valid in the running, clear after receiving the stop
commands
0x000
P08.45
UP
terminals
frequency
changing
ratio
0.01~50.00Hz/s
0.50
Hz/s
P08.46
DOWN
terminals
frequency
0.01~50.00 Hz/s
0.50
Hz/s
www.barghmaher.ir