Goodrive35 inverters Basic operation instruction
199
Function
code
Name
Detailed instruction of parameters
Default
value
1: S curve
P01.08
Stop mode
0:Decelerate to stop
1:Coast to stop
0
P01.09
Starting frequency of DC
braking
0.00Hz~P00.03(the Max. frequency)
0.00Hz
P01.10
Waiting time of DC
braking
0.00~30.00s
0.00s
P01.11
DC braking current
0.0~100.0%
0.0%
P01.12
DC braking time
0.0~50.0s
0.0s
P01.13
Dead time of FWD/REV
rotation
0.0~3600.0s
0.0s
P01.14
Shifting between
FWD/REV rotation
0:Switch after zero frequency
1:Switch after the starting frequency
2:Switch after the stopping speed and
delay
0
P01.15
Stopping speed
0.00~100.00Hz
0.20 Hz
P01.16
Detection of stopping
speed
0: Speed setting (the only detection
method in SVPWM mode)
1: Speed detecting value
0
P01.18
Terminal
running protection when
powering on
0:The terminal running command is
invalid when powering on
1: The terminal running command is
valid when powering on
0
P01.19
Action if running
frequency< lower limit
frequency
(valid >0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
3: Run at zero frequency
0
P01.20
Hibernation restore delay
time
0.0~3600.0s (valid when P01.19=2)
0.0s
P01.21
Restart after power off
0: Disable
1: Enable
0
P01.22
The waiting time of restart
after power off
0.0~3600.0s(valid when P01.21=1)
1.0s
P01.23
Start delay time
0.00~60.00s
0.00s