Goodrive35 inverters Basic operation instruction
215
Set
value
Function
Instructions
middle frequency)
the middle frequency.
28
Counter reset
Counter clear
29
Torque control disabling
The inverter shifts from torque control mode to speed
control mode.
30
ACC/DEC disabling
Ensure the inverter will not be affected by the external
signals (except for the stopping command) and keep
the current output frequency.
31
Counter trigging
Enable the pulse counter.
32
Length reset
Length counter clear
33
Frequency
increasing/decreasing setting
temporal clear
When the terminal closes, the frequency set by
UP/DOWN can be cleared. All set frequency will be
restored into the given frequency by the frequency
command channel and the frequency will come back
to the value after the frequency increasing or
decreasing.
34
DC braking
The inverter will begin DC braking after the valid
command.
35
Switch between motor1 and
motor2
Motor-shifting can be controlled after the terminal is
valid.
36
Switch commands to keypad
After the function terminal become valid, the running
command channel will be shifted into keypad running
command channel and the running command channel
will come back to the original state if the function
terminal is invalid.
37
Switch commands to
terminals
After the function terminal become valid, the running
command channel will be shifted into terminal running
command channel and the running command channel
will come back to the original state if the function
terminal is invalid.
38
Switch commands to
communication
After the function terminal become valid, the running
command channel will be shifted into communication
running command channel and the running command