Goodrive35 inverters Fault tracking
251
Braking circuit fault or
damage to the braking pipes
The external braking resistor
is not sufficient
Check the braking unit and ,
change new braking pipe
Increase the braking resistor
Grounding
shortcut fault
1
The output of the inverter is
short circuited with the
ground.
There is fault in the current
detection circuit.
The actual motor power
sharply differs from the
inverter power.
Check if the connection of the
motor is normal or not
Change the hall
Change the main control panel
Set motor parameters correctly.
Grounding
shortcut fault
2
The output of the inverter is
short circuited with the
ground.
There is fault in the current
detection circuit.
The actual motor power
sharply differs from the
inverter power.
Check if the connection of the
motor is normal or not
Change the Hall
Change the main control panel
Set motor parameters correctly.
The load is too heavy or
stalled.
Check the load and ensure it is
normal. Increase the detection
time.
Check whether the control
parameters are normal.
The control parameters of
the synchronous motors not
set properly.
The autoturn parameter is
not right.
The inverter is not connected
to the motor.
Check the load and ensure it is
normal.
Check whether the control
parameter is set properly or not.
Increase the maladjustment
detection time.