AI1/AI2 are the voltage/current option 
(0~10V/0~20mA) which can be shifted by jumpers; 
while AI3 is voltage input (-10V~+10V). 
Note: when analog AI1/AI2 select 0~20mA input, the 
corresponding voltage of 20mA is 10V. 
100.0% of the analog input setting corresponds to 
the maximum frequency (function code P00.03) in 
forward direction and -100.0% corresponds to the 
maximum frequency in reverse    direction (function 
code P00.03)   
4:High-speed pulse HDI setting 
The frequency is set by high-speed pulse terminals. 
Goodrive35 series inverters provide 1 high speed 
pulse input as the standard configuration. The pulse 
frequency range is 0.00~50.00kHz. 
100.0% of the high speed pulse input setting 
corresponds to the maximum frequency in forward 
direction (P00.03) and -100.0% corresponds to the 
maximum frequency in reverse direction (P00.03). 
Note: The pulse setting can only be input by 
multi-function terminals HDI. Set P05.00 (HDI input 
selection) to high speed pulse input, and set P05.49 
(HDI high speed pulse input function selection) to 
frequency setting input. 
5:Simple PLC program setting   
The inverter runs at simple PLC program mode 
when P00.06=5 or P00.07=5. Set P10 (simple PLC 
and multi-step speed control) to select the running 
frequency, running direction, ACC/DEC time and the 
keeping time of corresponding stage. See the 
function description of P10 for detailed information.   
6: Multi-step speed running setting 
The inverter runs at multi-step speed mode when 
P00.06=6 or P00.07=6. Set P05 to select the current