Goodrive35 inverters Function codes
58
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
AI1/AI2 are the voltage/current option
(0~10V/0~20mA) which can be shifted by jumpers;
while AI3 is voltage input (-10V~+10V).
Note: when analog AI1/AI2 select 0~20mA input, the
corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to
the maximum frequency (function code P00.03) in
forward direction and -100.0% corresponds to the
maximum frequency in reverse direction (function
code P00.03)
4:High-speed pulse HDI setting
The frequency is set by high-speed pulse terminals.
Goodrive35 series inverters provide 1 high speed
pulse input as the standard configuration. The pulse
frequency range is 0.00~50.00kHz.
100.0% of the high speed pulse input setting
corresponds to the maximum frequency in forward
direction (P00.03) and -100.0% corresponds to the
maximum frequency in reverse direction (P00.03).
Note: The pulse setting can only be input by
multi-function terminals HDI. Set P05.00 (HDI input
selection) to high speed pulse input, and set P05.49
(HDI high speed pulse input function selection) to
frequency setting input.
5:Simple PLC program setting
The inverter runs at simple PLC program mode
when P00.06=5 or P00.07=5. Set P10 (simple PLC
and multi-step speed control) to select the running
frequency, running direction, ACC/DEC time and the
keeping time of corresponding stage. See the
function description of P10 for detailed information.
6: Multi-step speed running setting
The inverter runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the current
www.barghmaher.ir