running stage, and set P10 to select the current
running frequency.
The multi-step speed has the priority when P00.06 or
P00.07 does not equal to 6, but the setting stage can
only be the 1~15 stage. The setting stage is 0~15 if
P00.06 or P00.07 equals to 6.
7: PID control setting
The running mode of the inverter is process PID
control when P00.06=7 or P00.07=7. It is necessary
to set P09. The running frequency of the inverter is
the value after PID effect. See P09 for the detailed
information of the given source, given value,
feedback source of PID.
8:MODBUS communication setting
The frequency is set by MODBUS communication.
See P14 for detailed information.
9:PROFIBUS/CANopen communication setting
The frequency is set by PROFIBUS/ CANopen
communication. See P15 for the detailed
information.
10:Ethernet communication setting(reserved)
See P16 for the detailed information.
11:Reserved
12:Pulse string AB setting
0:Maximum output frequency, 100% of B frequency
setting corresponds to the maximum output
frequency
1: A frequency command, 100% of B frequency
setting corresponds to the maximum output
frequency. Select this setting if it needs to adjust on
the base of A frequency command
0: A, the current frequency setting is A frequency
command
1: B, the current frequency setting is B frequency