Goodrive35 inverters Function codes
79
Detailed instruction of parameters
Weakening
coefficient
in constant
power
zone
The usage of AM in weakening control.
Function code P03.22 and P03.23 are effective at
constant power. The motor will enter into the
weakening state when the motor runs at rated
speed. Change the weakening curve by modifying
the weakening control coefficient. The bigger the
weakening control coefficient is, the steeper the
weak curve is.
The setting range of P03.22: 0.10~2.00
The setting range of P03.23: 5%~50%
Lowest
weakening
point in
constant
power
zone
P03.24 set the Max. Voltage of the inverter, which is
dependent on the site situation.
The setting range:0.0~120.0%
Preactivate the motor when the inverter starts up.
Build up a magnetic field inside the inverter to
improve the torque performance during the starting
process.
The setting time:0.000~10.000s
0~8000
Note: P03.24~P03.26 are invalid for vector mode.
Integral
gain of the
weak
magnetic
The response is relative to P03.26 and P03.27. It
can be adjusted.
Setting range: 0~8000
0x000~0x112
Ones: Control mode selection