Goodrive35 inverters Function codes
89
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
52: Pulse input disabled
53: Position deviation clear
54: Position proportional gain switch
55: Digital position cycle positioning enabled
56: E-stop
57: Motor overtemperature fault input
58: Rigid tapping enable
59: Switch to SVPWM control
60: Switch to FVC control
61:PID pole switching
62: Undervoltage stopping input
63: Reserved
P05.10
Polarity
selection
of the input
terminals
The function code is used to set the polarity of the
input terminals.
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT8
BIT7
BIT6
BIT5
HDI
S8
S7
S6
BIT4
BIT3
BIT2
BIT1
BIT0
S5
S4
S3
S2
S1
The setting range:0x000~0x1FF
0x000
P05.11
ON-OFF
filter time
Set the sample filter time of S1~S8 and HDI
terminals. If the interference is strong, increase the
parameter to avoid the disoperation.
0.000~1.000s
0.010s
P05.12
Virtual
terminals
setting
0x000~0x1FF(0: Disabled, 1:Enabled )
BIT0:S1 virtual terminal
BIT1:S2 virtual terminal
BIT2:S3 virtual terminal
BIT3:S4 virtual terminal
BIT4:S5 virtual terminal
BIT5:S6 virtual terminal
BIT6:S7 virtual terminal
0x000