Goodrive270 series VFD for fan and pump    Basic operation guidelines 
-109- 
four groups of ACC/DEC time. 
Used to clear the previous PLC state memory information 
and restart the simple PLC process. 
Used to pause the simple PLC. When the function is 
revoked, the simple PLC resumes the running. 
PID is ineffective temporarily, and the VFD maintains 
current frequency output. 
Switch between speed 
control and torque control 
The VFD switches from torque control mode to speed 
control mode, or vice versa. 
Used to ensure the VFD is not impacted by external signals 
(except for stop command), and maintains the present 
output frequency. 
Used to enable the counter to count pulses. 
Clear the frequency 
increase/decrease setting 
temporarily 
When the terminal is closed, the frequency value set by 
UP/DOWN can be cleared to restore the reference 
frequency to the frequency given by frequency command 
channel; when the terminal is opened, it restores to the 
frequency value after frequency increase/decrease setting. 
The VFD starts DC brake immediately after the command 
becomes valid. 
Switch between motor 1 
and motor 2 
When the function is enabled, you can realize switchover 
control of two motors. 
Switch the running 
command channel to 
keypad 
When the function is enabled, the running command 
channel is switched to keypad. When the function is 
disabled, the running command channel is restored to the 
previous setting. 
Switch the running 
command channel to 
terminal 
When the function is enabled, the running command 
channel is switched to terminal. When the function is 
disabled, the running command channel is restored to the