Goodrive270 series VFD for fan and pump Basic operation guidelines
-135-
Related parameter list:
Function
code
Name
Description
Value
Modify
P94.00
HVAC function
selection
0: Invalid
1: Valid
1
P94.10
Variable-frequency
motor run mode
0: Fixed
1: Circular
1
P94.11
Total number of
motors
08: Corresponding to motors
AH. The sequence numbers
must be successive.
4
P26.06
RO5 output
047: Same as those for standard
models
48: Fire mode activated
49: Pre-alarm of PID1 feedback
too low
50: Pre-alarm of PID1 feedback
too high
51: VFD in sleep
52: PID2 in running
53: PID2 stop
54: Indication of run with backup
pressure
55: Water shortage indication of
inlet pool
56: Pre-alarm
57: Control variable-frequency
circulation pump A
58: Control variable-frequency
circulation pump B
59: Control variable-frequency
circulation pump C
60: Control variable-frequency
circulation pump D
61: Control variable-frequency
circulation motor E
62: Control variable-frequency
circulation motor F
63: Control variable-frequency
circulation motor G
57
P26.07
RO6 output
58
P26.08
RO7 output
59
P26.09
RO8 output
60