Goodrive270 series VFD for fan and pump Function parameter list
-159-
Function
code
Name
Description
Default
Modify
Sleep
Run
Set frequency curve:
Running frequency curve:
t1 < P01.20, the VFD does not run
t0=P01.34, sleep delay
Run
t2
t1
t0
Frequency lower
limit f0
Frequency f
Time t
Coast to
stop
t1+t2 ≥P01.20, the VFD runs
Setting range: 0.0–3600.0s (Valid only when
P01.19=2)
P01.21
Power-off restart
selection
The function code indicates whether the VFD
automatically runs after re-power on.
0: Disable
1: Enable. If the restart condition is met, the VFD
will run automatically after waiting the time
defined by P01.22.
0
â—‹
P01.22
Wait time for restart
after power-off
The function code indicates the wait time before
the automatic running of the VFD that is
re-powered on.
Output frequency
Running
Power off
Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.0–3600.0s (Valid only when
P01.21=1)
1.0s
â—‹
P01.23
Start delay
After a VFD running command is given, the VFD
is in standby state and restarts with the delay
defined by P01.23 to implement brake release.
Setting range: 0.0–600.0s
0.0s
â—‹
P01.24
Stop speed delay
0.0–600.0s
0.0s
â—‹
P01.25
Open-loop 0Hz
output selection
0: Output without voltage
1: Output with voltage
2: Output with the DC braking current for stop
0
â—‹
P01.26
DEC time for
emergency stop
0.0–60.0s
2.0s
â—‹

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals