Goodrive270 series VFD for fan and pump Function parameter list
-200-
Function
code
Name
Description
Default
Modify
P08.14
Jump frequency
amplitude 3
function is invalid.
Set frequency f
Time t
Jump
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Setting range: 0.00HzP00.03 (Max. output
frequency)
0.00Hz
P08.15
Amplitude of
wobbling frequency
0.0100.0%
0.0%
P08.16
Amplitude of
sudden jump
frequency
0.050.0%
0.0%
P08.17
Rise time of
wobbling frequency
0.13600.0s
5.0s
P08.18
Fall time of
wobbling frequency
0.13600.0s
5.0s
P08.19
Switching frequency
of ACC/DEC time
0.00HzP00.03 (Max. output frequency)
0.00Hz: No switchover
If the running frequency is greater than P08.19,
switch to ACC/DEC time 2.
0.00Hz
P08.20
Frequency
threshold of the
start of droop
control
0.0050.00Hz
2.00Hz
P08.21
Reference
frequency of
ACC/DEC time
0: Max. output frequency
1: Set frequency
2: 100Hz
Note: Valid only for straight-line ACC/DEC
0
P08.22
Output torque
calculation method
0: Based on torque current
1: Based on output power
0
P08.23
Number of decimal
points of frequency
0: Two
1: One
0
P08.24
Number of decimal
points of linear
0: No decimal point
1: One decimal points
0