Goodrive270 series VFD for fan and pump Function parameter list
-201-
Function
code
Name
Description
Default
Modify
speed
2: Two decimal points
3: Three decimal points
P08.25
Set counting value
P08.2665535
0
P08.26
Designated
counting value
0P08.25
0
P08.27
Set running time
065535min
0min
P08.28
Auto fault reset
count
Auto fault reset count: When the VFD uses
automatic fault reset, it is used to set the number
of automatic fault reset times. When the number
of continuous reset times exceeds the value, the
VFD reports a fault and stops.
Auto fault reset interval: Time interval from when
a fault occurred to when automatic fault reset
takes effect.
After VFD starts, If no fault occurred within 600s
after the VFD starts, the number of automatic
fault reset times is cleared.
P08.28 setting range: 010
P08.29 setting range: 0.13600.0s
0
P08.29
Auto fault reset
interval
1.0s
P08.30
Frequency
decrease ratio in
drop control
The output frequency of the VFD changes as the
load changes. The function code is mainly used
to balance the power when several motors drive
a same load.
Setting range: 0.0050.00Hz
0.00Hz
P08.31
Channel for
switching between
motor 1 and motor 2
0x000x14
Ones place: Switchover channel
0: Terminal
1: Modbus communication
2: PROFIBUS/CANopen communication
3: Ethernet communication
4: PROFINET communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
0x00
P08.32
FDT1 electrical
level detection
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
50.00Hz