Goodrive270 series VFD for fan and pump Function parameter list
-205-
Hundreds place: Action selection for stop
0: Setting is valid.
1: Valid during running, cleared after stop
2: Valid during running, cleared after a stop
command is received
Frequency
increment integral
rate of the UP
terminal
Frequency integral
rate of the DOWN
terminal
Action selection at
power-off during
frequency setting
0x000–0x111
Ones place: Action selection at power-off during
frequency adjusting through digitals.
0: Save the setting at power-off.
1: Clear the setting at power-off.
Action selection at power-off during frequency
adjusting through Modbus communication
0: Save the setting at power-off.
1: Clear the setting at power-off.
Hundreds place: Action selection at power-off
during frequency adjusting through DP
communication methods
0: Save the setting at power-off.
1: Clear the setting at power-off.
Initial electricity
consumption MSB
Used to set the initial electricity consumption.
Initial electricity consumption = P08.48*1000 +
P08.49
P08.48 setting range: 0–59999 kWh (k)
P08.49 setting range: 0.0–999.9 kWh
Initial electricity
consumption LSB
Used to enable magnetic flux braking.
0: Invalid
100–150: A larger coefficient indicates stronger
braking.
The VFD can quickly slow down the motor by
increasing the magnetic flux. The energy
generated by the motor during braking can be