Goodrive270 series VFD for fan and pump Basic operation guidelines
-65-
Channel of
running
commands
P00.01
Multifunction
terminal function 36
Switch the running
command channel
to keypad
Multifunction
terminal function 37
Switch the running
command channel
to terminal
Multifunction
terminal function 38
Switch the running
command channel
to communication
Note: "/" indicates this multifunction terminal is invalid under present reference channel.
Related parameter list:
0: Sensorless vector control (SVC) mode 0
1: Sensorless vector control (SVC) mode 1
2: Space voltage vector control mode
Note: Before using a vector control mode (0 or 1),
enable the VFD to perform motor parameter
autotuning first.
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
Communication
mode of running
commands
0: Modbus
1: PROFIBUS/CANopen
2: Ethernet
3: PROFINET
4: Reserved
5: Wireless communication card
Motor parameter
autotuning
0: No operation
1: Dynamic autotuning 1; comprehensive motor
parameter autotuning. It is recommended to use
rotating autotuning when high control accuracy is
required.
2: Complete parameter static autotuning; complete
parameter static autotuning is used in cases where
the motor cannot be disconnected from load.
3: Partial parameter static autotuning; when the
present motor is motor 1, only P02.06, P02.07, and
P02.08 are autotuned; when the present motor is