Goodrive300-21 integrated machine for air compressor Function description
-56-
ensure the running current of the master will
not exceed automatic frequency reduction
threshold.
Time-out time of
maintenance
0–8000h
When this parameter is set to "0", the
maintenance time-out function is invalid. If it is
set to non-zero value, then the system will
release maintenance time-out pre-alarm by
changing BIT11 of P19.14 to 1 in cases where
the working time, after part maintenance
pre-alarm, exceeds the value set by P18.45.
Maintenance set
time of part 1
P19.00–P19.04 displays the set value of
maintenance time on five kinds of parts.
When the accumulated working time of the
part exceeds the corresponding set value,
the system will release pre-alarm by
changing the BIT of P19.14 to 1. If set to "0",
working time pre-alarm of the parts will be
invalid.
P19.05–P19.09 displays the working hours of
corresponding parts.
Range: 0–65535h
Maintenance set
time of part 2
Maintenance set
time of part 3
Maintenance set
time of part 4
Maintenance set
time of part 5
Actual output power
of motor
It displays the output frequency of the motor
and can be calibrated by setting P18.22.
Range: 0.0–6553.5kW
Displays the exhaust pressure value detected
currently.