Technical data
Page 37
4 Technical data
4.1 General Technical data
Table 5: Technical data: Ambient conditions and qualification
Range
Values
Admissible temperature ranges Storage temperature: -25 °C to +70 °C
Operating temperature: 0 °C to +40 °C
+40 °C to +50 °C at reduced power 2,5 %/K
Admissible installation height Mounting height maximum 2000 m above msl, above 1000 m
above msl with power reduction 1% per 100 m
Humidity Relative humidity up to 90 %, not bedewing
Protection degree IP20
Protection class I
Pollution degree 2
CE conformity
Low-voltage directive:
EMC directive:
2006/95/EC
verified by application of the harmonised standard EN 61800-5-1
2004/108/EC
verified by application of the harmonised standard EN 61800–3
cULus certification Listed according to UL 508C, C22.2 No. 274-13
Table 6: Technical data: Dimensions and weight
Type
Controller C 1-02
Controller C 1-05
Controller C 1-08
Dimensions including the
mounting plate (H*W*D)
261 mm*54,6 mm*205 mm
Dimensions (H*W*D) 200 mm*54 mm*200 mm
Weight approx. 2,0 kg approx. 2,1 kg
approx. 1,8 kg

Table of Contents