Non –valid for Mode - Actuator
04
04 START VALUE
OFF
Regulation Restart Value
Possible settings: 0 – 100 % – OFF
This parameter determines the start value after pump stop in percentage of the required
value.
e.g. REQUIRED VALUE [02]: 5.0 bar
START VALUE [04]: 80 % --> 4.0 bar
If the pump system has reached the required pressure of 5.0 bar and there is no more
consumption, the HYDROVAR shuts off the pump.
When the consumption increases, and the pressure drops the pump normally starts. If a
START VALUE [04] of 4.0 bar has been selected the pump won’t start before the pressure
drops below.
The following parameters in the main-menu are valid for all selected Modes:
05
05 LANGUAGE
ENGLISH
Language selection
Possible settings: To select the desired language press ▲ or ▼
The information on the display and all parameters can be called up in various languages.
The languages available are split in different blocks which support different languages.
Which of the available region block is included in your HYDROVAR could be seen in the
Type designation code. For detailed information see chapter 4.