EasyManuals Logo

ITT HYDROVAR Series User Manual

ITT HYDROVAR Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
53
With the following two parameters the current date and time, has to be set. That is
necessary to save and display failure messages with the accurate date and time when the
failure happened.
06
06 DATE
DD.MM.YYYY
Current Date
Set the date by pressing for approx. 3 sec.
After Pressing you will enter a Submenu where the current DAY / MONTH / and YEAR
can be set.
07
07 TIME
HH:MM
Current Time
Set the time by pressing for approx. 3 sec.
Enter the submenu by pressing to set current HOUR and MINUTE.
08
08 AUTO - START
ON
Auto Start
Possible settings: ON – OFF
Select ON with or OFF with the button.
If AUTO-START = ON, the HYDROVAR starts automatically (in case of demand) after a
remedy of a failure or disconnection of the power supply.
If AUTO-START = OFF, the HYDROVAR won’t start automatically after a remedy of a failure
or disconnection of the power supply.
After remedy of the failure or reconnection of the power supply the following message is
shown:
ITT XX.X Hz
STOP X.XX Bar
Press to restart the HYDROVAR.
09
09 OPERAT. TIME
0000 h.
Operating Hours
Total time the HYDROVAR is being connected to the power supply. How to reset see
Parameter CLR OPERAT. [1135].