82
0830
0830 ACTUAT.FRQ 1
XX.X Hz
Required frequency 1 for Actuator (digital)
Possible settings: 0.0 – MAX. FREQ. [0245]
Set the frequency with either or
The selected frequency in this parameter is only active in the Actuator mode if Parameter
C.REQ.VAL.1 [0805] is set to digital, and Parameter SW REQ.VAL [0815] is set to Setpoint 1
or the ACTUATOR FREQUENCY 1 is selected via digital input.
0835
0835 ACTUAT.FRQ 2
XX.X Hz
Required frequency 2 for Actuator (digital)
Possible settings: 0.0 – MAX. FREQ. [0245]
Set the frequency with either or
The selected frequency in this parameter is only active in the Actuator mode if Parameter
C.REQ.VAL.2 [0810] is set to digital, and Parameter SW REQ.VAL [0815] is set to Setpoint 2
or the ACTUATOR FREQUENCY 2 is selected via digital input.