4 3 KEB COMBIVERT F4-F
12
Name: Basis
15.12.98
CP - Parameter
© KEB Antriebstechnik, 1998
All Rights reserved
Operation
Chapter Section Page Date
Value Error / Status Response of the drive
massage
0 E.EF modulation immediately switched off
! To restart remove error and activate Reset !
1 A.EF quick stop / modulation switched off after speed 0 is
reached
! To restart remove error and activate Reset !
2 A.EF quick stop / holding tourqe at speed 0
! To restart remove error and activate Reset !
3 A.EF modulation immediately switched off
! Automatic restart, when error is no longer present
!
4 A.EF quick stop / modulation switched off after speed 0 is
reached
! Automatic restart, when error is no longer present
!
5 A.EF quick stop / holding tourqe at speed 0
! Automatic restart, when error is no longer present
!
6 none no effect on the drive
! Fault is ignored !
Behaviour at External Fault This parameter determines how the drive reacts to an external error (digital Input I3).
Adjustment Range: 0…6
Resolution: 1
Factory setting: 0
Customer setting: ________
Note: ENTER-Parameter
Quick stop
⇒⇒
⇒⇒
⇒
deceleration at the torque limit (CP.9)