GB - 83
Connection Power Unit R6-S
F3 Precharging fuse gG/gL or automatic circuit breaker with characteristic K dimensioned for the sum
oftheprechargingcurrents(here20A)
F4 10 A fuse gG/gL
F5
2)
DCfusestypeaR(seetechnicaldata)
F1, F2
2)
DC fuses type aR/gR ThecablecrosssectionaswellastheDCfuses(seechapter2.1)must
bedimensionedtotheDCratedcurrentoftheload(seetechnicaldataof
theinverter).
G1, G2 Regenerative unit COMBIVERT R6-S
X1A
Power circuit terminals
X1B
Connection for precharging and switching-on of line contactor K1, K3
X2A
Controlterminalstrip(X2A.12:controlrelease;X2A.17:voltageoutput)
X2B
Connection for synchronization line
X2C
Activationoftheself-holdingoftheloadshuntrelay(K2internal)
G3, G4 Frequencyinverteralltypes(see4.3.1)
H Supply of the signalling device
H1 Error message contactor K1 not dropped
H2 Error message contactor K2 not dropped
HF1,
HF2
Radiointerferencelter
K1, K3 Line contactor with auxiliary contacts
M Motor
S1 Onswitch/contactor(400V/32AAC3)designedtosumofprecharging
S2, S3 Realize control release with PLC or pre-charging contactor / -switch
1) In case of parallel connection of R6-S the total power can be smaller up to 10 % caused by pro-
duction tolerances of the commutation reactor. The impedance voltages uk of the commutation
reactor must be the same in case of parallel connection of R6-S with different sizes.
2) Mains- and DC fuses must be monitored.
Figure 35: Power supply and regenerative operation at parallel operation of up to three
R6-S
Parallel operation
When connecting in parallel operation, the parameter defaults record must be
changed.SeeapplicationinstructionsR6-Sunder„SpecialFunctionsforthepar-
allel connection“.