E 33
ANTRIEBSTECHNIK
Behaviour at External Fault
This parameter determines the
response of the drive to an external
fault.
Setting range: 0…6
Resolution: 1
Factory setting: 0
Remarks: ENTER-Parameter
Customer setting:
Value Response of Drive
0 Error message: E.EF → Immediate disconnection of inverter!
!
To restart eliminate the fault and make a
Reset !
1 Status message: A.EF → Fast stop → Disconnection of inverter after
attaining speed 0.
!
To restart eliminate the fault and make a
Reset !
2 Status message: A.EF → Fast stop → Holding torque at speed 0.
!
To restart eliminate the fault and make a
Reset !
3 Status message: A.EF → Immediate disconnection of inverter.
!
Automatic restart when fault condition no longer exists
!
4 Status message: A.EF → Fast stop → Disconnection of inverter after
attaining speed 0.
!
Automatic restart when fault condition no longer exists
!
5 Status message: A.EF → Fast stop → Holding torque at speed 0.
!
Automatic restart when fault condition no longer exists
!
6 Status message: none → No effect on the drive.
!
Fault is ignored
!
Permits the shifting of the setpoint-speed characteristic.
Offset REF 1
n
max
"forward"
n
max
"reverse"
+10 V
-10 V
3)
2) 1)
Setting range: -100…+100 %
Resolution: 0,1 %
Faxtory setting: 0 %
Customer setting: %
Examples:
Characteristic 1: CP.16 = 0% (standard setting)
0V = 0 U/min
Rotation "forward":n
max
is attained at +10V
Rotation "reverse":n
max
is attained at -10 V
Characteristic 2: CP.16 = +40%
0V = 40 % of n
max
"forward"
Rotation "forward":n
max
is attained at 60% of +10V
Rotation "reverse":maximal 60% of n
max
possible
Characteristic 3: CP.16 = –70%
0V = 70 % of n
max
"reverse"
Rotation "forward":maximal 30% of n
max
possible
Rotation "reverse":n
max
is attained at 30% of -10V
8. Parameter Description
Adjustment of parameter
CP.7 and CP.8 must be
observed!