E 34
Zero Point Hysteresis REF 1
A zero point hysteresis of the analog reference input REF1 is adjusted with this
parameter. Voltage fluctuations and ripple voltages around the zero point of the
setpoint value do not cause any drifting of the motor.
! Only when CP.7 or CP.8 > 0,00 s !
n
max
"forward"
+10 V
n
max
"reverse"
-10 V
Setting range: 0…10 %
Resolution: 0,1 %
Factory setting: 0 %
Customer setting: %
0…10 % = 0…+/- 1 V
Example: If CP.17 is adjusted to 5 % then the drive
starts only at a setpoint value of +/- 0,5 V.
Function Output A1
This parameter defines which varia-
ble is given out at analog output 1
(terminal X2.18).
Setting range: 0…6
Resolution: 1
Factory setting: 2
Remarks: ENTER-Parameter
Customer setting:
ValueOutput variable Value range at CP.19=1
0 actual speed -6000…+6000 U/min = -10V…+10V
1 apparent motor speed 0…25 A = 0…+10V
2 actual torque 0…25 Nm = 0…+10V
3 intermediate circuit voltage 0…1000 V = 0…+10V
4 speed reference variable -6000…+6000 U/min = -10V…+10V
5 system deviation (speed control) -6000…+6000 U/min = -10V…+10V
6 setpoint torque 0…25 Nm = 0…+10V5
^
^
^
^
^
^
^
Amplification Output A1
Parameter CP.19 defines the
amplifcation of the analog output
signal at output A1 (terminal X2.18).
Setting range: -20…+20
Resolution: 0,01
Factory setting: 3 x M
Rated
= +10 V
Customer setting:
^
1)
2)
3)
+10 V
-10 V
- n
+n,I,U,M
Characteristic 1: Amplification factor 1
Characteristic 2: Amplification factor 2
Characteristic 3: Amplification factor 0,5
At 2000 U/min a measurement shall be taken at analog output A1 +10 V.
value at amplification 1 ( s. CP.18 ) 6000 U/min
CP.19 = ––––––––––––––––––––––––––––– = ––––––––––– = 3
desired value at +10V 2000 U/min
Calculation Example:
8. Parameter Description
Adjustment of parameter
CP.7 and CP.8 must be
observed!