Chapter 2: Front panel programming
36 P/N 3102351-EN • REV 005 • ISS 28DEC18
Programmable
feature or option
Possible settings Listing
Agency
Permitted
(Y/N)
Permitted
settings
Panel default
0 to 300 seconds
through release
correlation; 10, 20, 30,
40, 50 seconds on REL
module
UL, ULC Y 0 to 60 seconds
(combined)
0 seconds in
release
correlation; 50
seconds on
REL module
0 to 300 seconds
through abort
correlation: 0, 10
seconds on REL
module
UL, ULC Y 0 to 60 seconds
(combined) for all
abort modules
0 seconds in
abort
correlation; 10
seconds on
REL module
Carbon monoxide (CO)
signaling
Input: (CO element of
the detector):
CO Alarm
CO Supervisory
CO Monitor
Output: Channel 2 of
T3T4 module
UL, ULC Y Input: (CO element
of the detector) [5]:
CO alarm
Output: Channel 2
of T3T4 module
No default
correlation
with a
Zone event
notification Type
Alarm, Monitor,
Supervisory, Waterflow
Alarm, Monitor,
Supervisory, Waterflow
UL
ULC
Y
Y
Alarm, Monitor,
Supervisory,
Waterflow
Supervisory [6]
Alarm
Alarm
[1] Allowed only if the IDC is connected to the latching alarm device
[2] Allowed only when the supervising station supervises the telephone line and annunciates fault conditions
within 200 seconds
[3] Prohibited when the control panel is connected to a supervising station
[4] The power supplies BPS6A, BPS6A/230, BPS10A, BPS10A/230 used for SIGA-REL are not compatible with
FM sprinkler applications that require 90 hours of standby.
[5] CO alarm signals are required to activate TC4 CO evacuation signals but CO Supervisory or CO Monitor
signals are not allowed to activate CO evacuation signals. CO alarm/CO supervisory/CO monitor signals shall not
activate TC3 fire evacuation signals.
[6] CO detectors with a “CO alarm” device type must be programed using zones with bicolor LEDs (zones 13
through 16 and 29 through 32) and the zone type must be set to Supervisory. The panel Event Notification must
be set to Zone. Using this configuration ensures that when the “CO alarm” device type goes active, the panel
displays a yellow LED indication instead of a red. This configuration complies with CAN/ULC-S527.
[7] UL 864 does not allow the use of alarm verified smoke detectors for activating releasing service applications.