Chapter 1: Installation and wiring
10 P/N 3102351-EN • REV 005 • ISS 28DEC18
Notification appliance circuit wiring (TB2)
The control panel provides either two or four notification appliance circuits depending on which
model you have. Each circuit can be individually configured for continuous, temporal,
synchronized, coded, or city tie output.
Circuit specifications
Class B or Class A.
Circuit voltage: 24 VFWR, regulated
Circuit current
VS1 panel:
3.75 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz input voltage
3.0 A total, 2.5 A max. per circuit at 230 VAC 50 Hz input voltage
VS4 panel:
6.0 A total, 2.5 A max. per circuit at 120/230 VAC 60 Hz input voltage
5.0 A total, 2.5 A max. per circuit at 230 VAC 50 Hz input voltage
Max. resistance: 26 Ω total
Max. capacitance: 0.35 µF
EOLR: 15 kΩ, 1/2 W (P/N EOL-15), ordered separately
Synchronization: For NACs wired Class A or Class B, signal synchronization is supported
system-wide (all NAC circuits).
Ground fault impedance: 0 to 5 kΩ
Power-limited and supervised
Notes
On the VS1 panel, Class A wiring is available only when the optional SA-CLA expansion
card is installed. Refer to the SA-CLA Class A Interface Card Installation Sheet
(P/N 3101094-EN) and to the topic “SA-CLA wiringon page 26.
Listed EOLRs must be installed as shown for proper supervision.
Marking indicates the output signal polarity when the circuit is active. Polarity reverses
when the circuit is not active. Wire notification appliances accordingly. Notification
appliance polarity is shown in the active state.
Installation limits are subject to acceptance by the AHJ.
If the riser is used for more than one notification zone, install in accordance with the
survivability from attack by fire requirements in NFPA 72 National Fire Alarm and Signaling
Code.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals