Chapter 5: Diagnostics, maintenance, and testing
178 P/N 3102351-EN • REV 005 • ISS 28DEC18
To test fire a device:
1. Press the Menu button and choose Test.
2. Choose Test Fire.
3. Enter a level one password.
4. Choose the loop the device is on.
Note: If the panel only has one loop, the loop selection screen does not display. Go to the
next step.
5. Enter the device number of the device you want to test fire.
6. Press Enter.
7. Choose Start to start the test.
8. When you have finished, press Reset (or repeat steps 1 to 7 and choose End) to clear the
test alarms and return the system to normal.
9. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
SA-DACT testing
A dialer test is a test of the telephone line for each dialer account. When a dialer is tested, a
normal or abnormal test message (depending on the state of the system) is sent to the
selected account. If the dialer is set up for dual line operation, a test message is sent to both
lines regardless of the success of the transmission for either account.
Note: Before conducting a test, configure the dialer’s accounts for proper operation.
To conduct a dialer test:
1. Press the control panel’s Menu button.
2. Choose Test.
3. Choose Dialer.
4. Enter a level one password.
5. Select the account that you want to test.
6. Press Enter.
The test message is sent to the CMS account that you selected. For verification of the CMS
account receiving the test message, you must be in contact with the CMS account during
the test. Nothing is displayed on the LCD.