Chapter 2: Front panel programming
62 P/N 3102351-EN • REV 005 • ISS 28DEC18
Note: The current language, marketplace, and loop device configuration settings are not
affected by the Restore Defaults command.
To restore the default settings:
1. Press the Menu button and choose Program.
2. Choose Restore Defaults.
3. Enter a level two password.
4. Select either Panel Only, CMS Only, or Panel and CMS.
Panel only: Restores only the panel’s defaults (panel operation and panel configuration
options)
CMS only: Restores only the dialer, network (1-8)
Panel and CMS: Restores both the panel and CMS device defaults
5. Press Enter.
6. Return to the Program menu.
7. Choose Panel Restart.
8. Choose Yes.
The panel restarts, and the factory default settings are reloaded into the database.
Setting up the programmable keys
There are two control panel buttons that can be assigned to correlation groups in order to:
• Disable a correlation group or members of a correlation group
• Activate and restore the outputs in a correlation group
• Unlatch all latched output devices globally
Notes
• You should not disable the REL device when it is part of a correlation group.
• You should not configure user keys as correlation group input devices.
By default, the buttons are not programmed. The buttons can be labeled to indicate their
function with a slip-in label. To operate the buttons, you must be logged on with a level one
password or greater.