Appendix C: Applications
P/N 3102351-EN • REV 005 • ISS 28DEC18 231
To program sounder bases for local alarm signaling:
1. Set the panel’s Event Notification option to Device.
2. Configure the smoke detectors as follows:
Message Line 1: SMOKE_<N>, where <N> can be the device address or other number
Base Type: Sounder
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm
3. Configure the polarity reversal module as follows:
Device Type: Relay Silence
Message Line 1: SOUNDER_RLY_1
Message Line 2: As required
4. Configure the RM1 or CT1 module as follows:
Device type: Monitor
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
5. Configure Correlation Group 001 as follows:
Add/Remove Zone: As required
Add/Remove NAC: Add all polarity reversal modules used to activate sounder bases
Add/Remove Device: Add all alarm signal initiating devices
In-suite signal silence applications
This section provides high level instructions for creating an in-suite signal silence application
based on the use of correlation groups. Additional background material and detailed
instructions are also available. See:
What is in-suite signal silence?on page 39
Programming in-suite signal silenceon page 88
What is a correlation group?on page 37
Correlation group programmingon page 83

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals