Appendix C: Applications
P/N 3102351-EN • REV 005 • ISS 28DEC18 231
To program sounder bases for local alarm signaling:
1. Set the panel’s Event Notification option to Device.
2. Configure the smoke detectors as follows:
Message Line 1: SMOKE_<N>, where <N> can be the device address or other number
Base Type: Sounder
Follow: None, Head, Alarm, Alm + Vrfy, or Alm + PreAlm
3. Configure the polarity reversal module as follows:
Device Type: Relay Silence
Message Line 1: SOUNDER_RLY_1
Message Line 2: As required
4. Configure the RM1 or CT1 module as follows:
Device type: Monitor
Message Line 1: 24VDC_RISER
Message Line 2: SOUNDER_RLY_1
5. Configure Correlation Group 001 as follows:
Add/Remove Zone: As required
Add/Remove NAC: Add all polarity reversal modules used to activate sounder bases
Add/Remove Device: Add all alarm signal initiating devices
In-suite signal silence applications
This section provides high level instructions for creating an in-suite signal silence application
based on the use of correlation groups. Additional background material and detailed
instructions are also available. See:
• “What is in-suite signal silence?” on page 39
• “Programming in-suite signal silence” on page 88
• “What is a correlation group?” on page 37
• “Correlation group programming” on page 83