Chapter 3: System operation
154 P/N 3102351-EN • REV 005 • ISS 28DEC18
• The LCD displays an event to indicate that the device is disabled.
• The common Trouble LED flashes and the panel goes into a trouble state.
• The common Trouble relay changes state.
• The disabled and active points indicators on the LCD increment. The event is transmitted
off-premises, if programmed to do so.
• Resetting the panel has no effect on disabled devices, but removing all power from the
panel clears the disable and enables the device.
To disable or enable a device:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Enable/Disable.
4. Choose Device.
5. Choose the loop the device is on.
Note: If the panel only has one loop, the loop selection screen does not display. Go to the
next step.
6. Enter the device ID for the device that you want to disable or enable.
7. Press Enter.
8. If the device is active, acknowledge the warning message by selecting Continue to disable
the device or Cancel to exit.
The device is disabled and a message indicating that the device is disabled is displayed on
the LCD.
9. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Disabling and enabling zones
Zones are typically disabled while maintenance is performed to prevent event messages
originating from the zone from being displayed, printed, or reported off-premises. Disabling a
zone does not prevent activations in the zone. All devices in the zone continue to function
normally.
Note: Remember to enable the zone as soon as you have finished working with it. Resetting
the panel does not restore disabled zones. These must be manually enabled and then
restored.