Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 91
Device programming
Each device that operates on a notification appliance circuit (NAC) or device loop has
operating parameters that must be set. This includes assigning a device type and label,
programming event notification, etc.
Note: Addressable devices are programmed by entering the address of the device to be
programmed, then setting the device options. It is important to have a printout of the Device
Details > Serial Number report to correlate the device address with the default label and serial
number. This will make device programming much easier. See “Device Details reporton page
169.
Table 26: Programming devices Device options
Option
Description
Zone
Identifies the zone to which the device will be added.
To add the device to a zone, enter the zone number.
or
If the device will not be added to a zone, select Off.
Note: Do not mix device and zone types. For example, do not place a nonlatching
supervisory device in an alarm zone. When the supervisory device activates and an alarm
event is initiated, the alarm event automatically clears when the device restores without
having to reset the panel.
Zone secondary
Identifies the zone to which the device’s secondary element (if it exists) will be added.
To add the device to a zone, enter the zone number.
or
If the device will not be added to a zone, select Off.
Note: Do not mix device and zone types. For example, do not place a nonlatching
supervisory device in an alarm zone. When the supervisory device activates and an alarm
event is initiated, the alarm event automatically clears when the device restores without
having to reset the panel. Be sure to name your zones appropriately in message line 1 for
CO activations.
Label
Contains the two lines of text displayed beneath the device number on the LCD.
1. Enter text for the device label (two lines of 20 characters).
2. When you have finished, choose Save.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217