Chapter 2: Front panel programming
74 P/N 3102351-EN • REV 005 • ISS 28DEC18
2. Enter a text label for the zone (two lines of 20 characters). The default label is “Zone XX.”
3. Press Enter to save the label and go to the next number of the zone.
Note: Pressing the Enter button saves the current label, and then goes to the next zone
number so that you can quickly go to each zone and label it.
4. Enter a text label for the zone (two lines of 20 characters).
5. Repeat steps 3 and 4 until all zones are labeled.
6. When you have finished labeling, make sure the cursor is on the zone number, and then
press the Cancel button to exit and go to the next auto programming option.
Performing incremental programming
Incremental programming lets you add and label devices and zones to an existing database
without affecting current settings. It is typically used to add or remove a device loop or a large
number of individual devices. Incremental programming should be used only after the panel
has been programmed either by auto programming or advanced programming.
Incremental programming options
Table 23 below describes the options to be set when performing incremental programming.
Table 23: Incremental programming options
Device option
Description
Loop
Select the loop (number) that you want to program, or select All to program all loops.
Label devices
Yes: Enables device labeling
No: Disables device labeling
Label zones
Yes: Enables zone labeling
No: Disables zone labeling
Follow
This option controls the conditions that will activate relay or sounder detector bases. Select
from the following values:
Head: The base is controlled by the detector’s settings.
The base activates when the detector goes into alarm, unless the detector is set for alarm
verification.
If the detector is set for alarm verification, the base activates when the detector goes into
alarm verification. It does not restore, however, until the alarm restores.
The base does not respond when the detector goes into prealarm no matter how the
detector is configured. Also, the base only follows the primary element of a dual element
detector. Any activation from a secondary element does not trigger the base.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals