Chapter 5: Diagnostics, maintenance, and testing
P/N 3102351-EN • REV 005 • ISS 28DEC18 179
7. Press Cancel to return to the previous menu.
or
Press the Menu button to exit menu mode.
Conducting a lamp test
A lamp test lights all of the LEDs on the panel and the LED annunciator and tests the LCD so
that you can verify proper operation. LEDs stay on for 15 seconds.
To conduct a lamp test:
1. Press the menu button and choose Test.
2. Choose Lamp Test.
3. Press Enter.
4. Verify that all LEDs on the panel, the LCD, and the LED annunciator (if used) work
properly.
Starting and stopping a walk test
A walk test lets you test individual zones or devices without having to create an actual alarm
condition. You can conduct a walk test in silent or audible mode. In silent mode, the audible
devices (NACs) do not sound. In audible mode, only the panel onboard NACs activate.
Addressable devices configured for use as a NAC are not affected.
Zones should be placed in walk test one at a time. This allows the balance of the system to
remain in service. When a device is activated for test, it remains active throughout the test and
does not restore until the walk test is ended. When the walk test is ended, all of the tested
devices restore.
Note: Walk test does not operate when the panel has an active alarm event.
When you enter walk test mode:
The Test LED is steady for an audible walk test and flashes for a silent walk test.
Walk Test is displayed on the LCD. Walk Test is replaced with the device activation
message during the period the device is activated while in walk test mode.
The panel enters a trouble state. There is no fire protection for the zone in walk test. If an
unselected zone or device goes into alarm or trouble, all programmed outputs operate as
programmed.
Zones and devices behave as follows during walk test.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217