Chapter 5: Diagnostics, maintenance, and testing
180 P/N 3102351-EN • REV 005 • ISS 28DEC18
For alarm events, the appropriate panel and annunciator LEDs and buzzers turn on. In the
audible (NAC) test mode a four-second pulse sounds for NAC types: continuous
nonsilenceable, continuous silenceable, Genesis nonsilenceable, Genesis with audible
silence only, and Genesis with audible and visible silenceable on the audible devices. A
single 3-3-3 cycle sounds for NAC types: temporal nonsilenceable, temporal silenceable,
coder basic, coder continuous, coder 120spm, and coder temporal on the audible devices.
For trouble events, the appropriate LEDs and the buzzers turn on. In the audible (NAC) test
mode a two-second pulse sounds on the audible devices.
For ground fault events, the appropriate LEDs and the buzzers turn on. In the audible
(NAC) test mode, a two-second pulse sounds on the audible devices.
All device activations are latched until walk test is ended or the panel is reset. When walk
test is ended, it takes approximately eight seconds for the devices to restore. If the device
being tested is in a zone and does not restore, the zone does not reset.
If auxiliary power is resettable, the auxiliary power is interrupted while the zone is reset.
Input zones programmed as waterflow with retard require 10 to 15 seconds of activation to
initiate the test signals.
Devices programmed as alarm verify and not in test mode go directly into alarm if activated
(the alarm verification process is bypassed).
Restore each device after testing. For example, if you are testing a pull station, reset the
pull station before testing the next device.
The panel terminates walk test if:
The zone or device being tested remains inactive for 30 minutes.
The walk test is stopped by the user.
To start a walk test:
1. Press the Menu button and choose Test.
2. Choose Walk Test Silent or Walk Test Audible.
3. Enter a level one password.
4. Choose either All Devices or Zone.
5. If you chose Zone, enter the zone ID for the zone you are going to conduct the walk test.
6. Choose Start.
7. Conduct your walk test.
8. Press Cancel to return to the previous menu.
or
Press the Menu button to exit menu mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217

Related product manuals