Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 65
8. If you chose Disable, press the down arrow to edit the Control option, and indicate what the
key should control. Choose:
Members
Corr Grp
Both
Press Enter to reopen the previous menu, and then choose Save.
Note: This option is not available for Unlatch, Activate, or Restore.
You are now ready to choose the correlation groups to be activated, disabled, or restored.
9. Enter the number of the first correlation group to be assigned or unassigned, and then
press Enter.
If you enter the number of a correlation group that is already assigned to the key, the
command REM (remove) is displayed. Pressing Enter removes the group from the list.
If you enter the number of a correlation group that has not yet been assigned to the key,
the command ADD is displayed. Pressing Enter adds the new group to the list.
10. Enter the number of the next correlation group to be added or removed, and then press
Enter. Repeat to add or remove any remaining correlation groups.
11. When you have finished editing the list of correlation groups, press Enter to reopen the
previous menu, and then choose Save.
or
Press the Menu button to cancel your changes and exit menu mode.
12. Press the Menu button to exit menu mode. The button is now programmed to activate,
disable, or restore all correlation groups that you have added to the list.
Note: Correlation groups with REL should not be configured for activate, restore, or
disable.
Clearing the event history log
The panel maintains a log of the most recent 1,000 system or user events. The event record
contains the event time, the event type, the event state, and the event ID. The event time is the
time and date of the event activation or restoration. All of these records are stored in the
panel’s history database and can be cleared (deleted) if needed. Once the history log exceeds
1,000 events, the oldest event is deleted as the newest event is added.
Once the history log is cleared, all new panel events are stored in history. You might want to
clear the history log in the following situations:
When installation is complete, you can clear the history log before turning the system over
to the building owner.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kidde VS Series and is the answer not in the manual?

Kidde VS Series Specifications

General IconGeneral
Power Source120V AC
Battery Backup9V battery
Sensor TypePhotoelectric
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
LED IndicatorYes
Mounting TypeWall or ceiling
ComplianceUL 217