Chapter 2: Front panel programming
58 P/N 3102351-EN • REV 005 • ISS 28DEC18
Description
Continuous nonsilenceable
(latched)
For latching strobes and notification appliances that generate a temporal pattern.
For strobes and notification appliances that generate a noncoded tone.
Genesis audible visible
silence
For Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced
Integrity appliances maintain synchronization per UL 1971. For Genesis devices
only, connected horns can be silenced and strobes turn off.
For Genesis and Enhanced Integrity horns and strobes. Genesis and Enhanced
Integrity appliances maintain synchronization per UL 1971. For Genesis devices
only, connected horns cannot be silenced and strobes on the same two-wire
circuit flash until the panel is reset. [2]
For relay devices that do not follow signal silence [2]
Relay nonsilenceable
(latched)
For relay devices that do not follow signal silence and do not restore until
manually unlatched
For relays that turn off when you press Signal Silence. [2]
For modules that output an unsynchronized signal and that do not turn off when
you press Signal Silence.
Supervised output (latched)
For latched output modules that output an unsynchronized signal and that do not
turn off when you press Signal Silence.
Auto sync output Silenceable
For generating sound patterns on SBT/ABDT sounder bases for carbon
monoxide (CO) and fire signals. Signals turn off when you press Signal Silence.
Only patterns from T3T4 are silenced.
Auto sync output
nonsilenceable
For generating sound patterns on SBT/ABDT sounder bases for carbon
monoxide (CO) and fire signals.
For output modules that are configured to manually unlatch latched outputs [1]
The following output modules can be configured to unlatch latched outputs: CT1, CT2, MAB, MCT2, MM1,
, or RZI16-2.
[2] Supports Standalone mode of operation.
Table 17: Latched output device types [1]
Description
nonsilenceable
For Class B latched output modules that output an unsynchronized signal. Does not
follow signal silence.
Relay nonsilence NC
(latched)
For relay devices functioning as latched output devices that open when activated.
Does not follow signal silence.
Relay nonsilence NO
(latched) latch
For relay devices functioning as latched output devices that close when activated.
Does not follow signal silence.
Relay nonsilenceable
(latched)
For Class B relay devices functioning as latched output devices. Does not follow
signal silence.