7.2.1 Wiring in Analog Speed Mode
Fig. 7-6 Wiring diagram of CD2S Servo in analogspeed mode
7.2.2 Parameters for Analog Speed Mode
Table 7-9 Parameters for analog speed mode
Numeric
Display
Variable Name
Meaning
Default
Value
Range
d3.22
Analog1_Filter
Used to smooth the input analog signals.
Filter frequency: f=4000/(2π*
Analog1_Filter)
Time Constant (T) = Analog1_Filter/4000
(S)
5
1~127
d3.23
Analog1_Dead
Sets dead zone data for external analog
signal 1
0
0~10V
d3.24
Analog1_Offset
Sets offset data for external analog signal 1
0
-10~10V
d3.25
Analog2_Filter
Used to smooth the input analog signals.
Filter frequency: f=4000/(2π*
Analog1_Filter)
Time Constant (T) = Analog2_Filter/4000
(S)
5
1~127
d3.26
Analog2_Dead
Sets dead zone data for external analog
signal 2
0
0~10V
d3.27
Analog2_Offset
Sets offset data for external analog signal 2
0
-10~10V