138
MA06-03-1-01
Menu
[Direct access: CMD -> 7084]
Parameter
[Direct access]
Description
Default
value
Value
Range
O:Standby
Definition of an output signalling the active
standby mode.
*Contact type:
Selection whether the inputs for the standby
mode signal are applied by normally close
contacts or normally open contacts.
N.O./N.C.
T:Standby (s)
Definition of a time in seconds when the standby
mode is to be activated.
300
0-999 s
T:switch on time (s)
Definition of the maximum delay time (in
seconds) for which, after switched back to
normal operation from standby, the installation
has to wait for a report about whether VVVF is
ready. Should no ready message be received in
this time, a controller error will be registered
and the lift will go out of operation.
0
0-999 s
I:Standby off
Definition of an input to switch off the standby
mode.
ΝΟ
I:Standby on
Definition of an input to switch on the standby
mode.
ΝΟ
I:VVVF ready
Definition of an input which signals the ready
state (after standby) of the inverter to the
controller.
ΝΟ