700 + Ok // Tools > Adjustment > Page 2 > Delete UCM erron
UCM was detected by speed
The controller checks the lift speed in the zone. If the measures speed value should be higher than the
one given in “Menu -> Parameter -> General settings -> UCM -> v UCM check” the controller will initiate
an emergency stop.
The controller switches into “out-of-order” mode.
- UCM detected
- approaching speed too high
- reading error of the absolute encoder
- parameters are not set correctly
- See causes
- Entering the value “0“ disables the speed monitoring
700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
UCM was detected by position
After leaving the zone the controller recognizes the shaft doors to be open (S6 not closed) and thus
detects a UCM situation.
The controller switches into “out-of-order” mode.
- UCM detected
- reading error of the absolute encoder
700 + Ok // Tools > Adjustment > Page 2 > Delete UCM error
This error serves for internal error analysis. // If this error should be displayed, please conduct a controller
reset.
The controller switches into “out-of-order” mode.
The controller recognizes a missing phase for the car light. At the connecting terminal L4 on the relay
board a 230V supply cannot be decteted.