The controller switches into “out-of-order” mode.
The lift stops in the current landing
The lift descends into the lowest landing
- phase failure
- wiring not correct
- defective input
- See causes
If the light monitoring should not be necessary one disable the monitoring via the menu „ Tools
-> Adjustment -> Surveillance -> Car light monitor j/n“
Notification that the car light switch has been switched off at the controller.
The controller switches into “out-of-order” mode.
The lift stops in the current landing
The lift descends into the lowest landing
- Car light switch is being activated
small head room to move up in inspection!
Notification that the Inspection end switch which is simulated by the software was reached during
upward travel.
- end switch has been reached
- leave the end switches by travelling downwards
- check parameters
Resolve error and enter 800+OK afterwards
Apron input not active in normal mode at door 1!
Under normal operation, the controller expects to receive input about the hinged apron being retracted.
The controller switches into “out-of-order” mode.
- hinged apron folded out
- wiring not correct
- defective input
- retract hinged apron
- in case of automatic folding, please note the operating procedures
If the input should be defective it can be parameterized to another available I/O any time.