3 sec. upon beginning of travel, the controller checks whether the monitoring contact of the descent
protection has opened; that is in case of an error the input “control descent protection” still applies.
The controller switches into “out-of-order” mode.
- activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input
- see causes
- check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.
3 sec. upon termination of travel, the controller checks whether the monitoring contact of the descent
protection has closed; that is in case of an error the input “control descent protection” is not applied.
The controller switches into “out-of-order” mode.
- activation of the descent protection does not function properly (see wiring diagram)
- wiring not correct
- defective input
- see causes
- check input on the status page
If the input should be defective it can be parameterized to another available I/O any time.
It is being referred to an IO which no function is assigned to.
Assign the desired function to the IO
A function was programmed on to a physically not existing module
- integrate the module into the installation
- program the function onto another module