Klereo Kompact installation manual V 3
34
Klereo
Parameters
Set-up Equipments Indoor pool
Pool cover
Pool cover polarity
Klereo filtering
Indoor pool: mark this option if the pool is indoor. When this option is selected, the Salt
Chlorinator production of Chlorine is default reduced by 80%. This reduction is adjustable
(menu: « water treatment », «advanced parameters », « indoor pool ratio »).
Pool cover: mark this option when there is a pool cover. When this option is selected, the Salt
Chlorinator production of Chlorine is reduced by 80%. This option is default selected when
delivered. This reduction is adjustable (menu: « water treatment », advanced parameters »,
“pool cover ratio”).
Pool cover polarity: depending if the pool cover contact is normally open or closed. When this
option is selected, the contact is normally open (i.e. pool cover closed
contact open)
Klereo filtering: this function is selected when delivered. Indeed, it is Klereo default piloting
filtering. However filtering can also be controlled by an external device: in that case disable
the mark.
5.12 Outputs assignment
Klereo Kompact outputs are default set up when delivered.
Specify the type of equipments connected to the Klereo Kompact system by going to the
menu ”Output assignment”.
Klereo
Parameters
Set-up
Outputs assignment
P-Q. assignment
n.
S-SN assignment
R-RN assignment
M /K-KN assignment
Aux.A designation
IMPORTANT
If Klereo filtering is disabled, water treatment will only be ON when:
The Klereo control box detects a water flow: in that case, set-up the flow-switch in
“treatment validation”
Or
There is 220V detected on input I-J (Klereo control box unit power supply input).
In that case:
- Connect the filter pump 220V on the input I-J and set-up the 220V input in
« filtering slave mode” (go to menu “parameters”/ “set-up” / “Inputs set-up”/ 220V
input and mark “ slave filtering” ).
- Do not disable the flow switch function (do not mark “None” in the menu
“parameters”/ “set-up” / “Inputs set-up”/ Flow switch)
We advise that you program 2 hours filtering cycles
minimum.